UK Code:
2CFC
Harmonised Code:
EN50200
Usage:
Fire alarms, emergency lighting and critical systems
Standards:
BS 7629-1:2015 Standard 60
Certifications:
CE, UKCA, BASEC
Warranty:
12 Months
Packaging Description:
Drum (plastic)
Core Size (mm):
4
Number of Strands:
1
Conductor Type:
Solid Copper
Conductor Class:
Class 1
Cable Profile:
Round
Low Smoke Zero Halogen:
Yes
Armoured:
No
Indoor/Outdoor Usage:
Indoor
Insulation Material:
Fire resistant silicone
Outer Sheath Material:
Low smoke zero halogen (LSZH) thermoplastic
Filler Material:
N/A
Braiding Material:
N/A
Screen Material:
Aluminium foil
Armour Material:
N/A
Overall Cable Diameter (mm):
11.9
Cut Length (m):
100
Minimum Bending Radius:
6 x D
Nominal Cross Section Area (mm²):
2 x 4.0
Diameter of Conductor (mm):
4
Conductor Cross Section Area (mm²):
4
Net Weight kg per km (kg):
200
Outer Sheath Colour:
White
Inner Core Colour(s):
Brown, Blue
Minimum Operating Temperature (ºC):
-40º C
Maximum Operating Temperature (ºC):
90º C
Maximum Short Circuit Temperature (ºC):
250º C
Rated Voltage Uo/U (V):
300/500 V
Conductor DC Resistance at 20ºC:
4.61 Ω/km
Maximum Mass Supportable - Twin flexible cord (kg):
0
EV Charging:
N/A
Number of Phases:
Single
Capacity Ref Method B: 2 cables/single phase AC/DC (A):
30
Capacity Ref Method C: 2 cables/single phase AC/DC (A):
36
Voltage Drop per A per m: DC or single phase AC (mV/A/m):
11
Capacity Ref Method 100 (A):
N/A
Capacity Ref Method 101 (A):
N/A
Capacity Ref Method 102 (A):
N/A
Capacity Ref Method 103 (A):
N/A