For prices call us on 01908 272444 or contact your sales representative. 

 


3093Y 3 Core Heat Resistant Flex (White with Brown, Blue, Green/Yellow) 1.5mm² x 25m

SKU:
3093Y1.5W25

Product Description


Supply leads for use as 318-Y but particularly for use in high temperature zones, for internal wiring or supply cords to electrical apparatus. Not suitable for outdoor use. Fine stranded copper core.
  • 1.5mm² Fine-Stranded Copper core
  • Rated Voltage: 300/500 V
  • Usage: Storage heaters and heating elements
  • Packaging: Coil
  • Certifications & Standards: CE, HAR, UKCA / BS EN 50525-2-11
  • Other Details

    UK Code:
    3093Y
    Harmonised Code:
    H05V2V2-F
    Usage:
    Storage heaters and heating elements
    Standards:
    BS EN 50525-2-11
    Certifications:
    CE, HAR, UKCA
    Warranty:
    12 Months
    Packaging Description:
    Coil
    Core Size (mm):
    1.5
    Number of Strands:
    27
    Conductor Type:
    Fine-Stranded Copper
    Conductor Class:
    Class 5
    Cable Profile:
    Round
    Low Smoke Zero Halogen:
    No
    Armoured:
    No
    Indoor/Outdoor Usage:
    Indoor
    Insulation Material:
    High temperature resistant polyvinyl chloride (PVC)
    Outer Sheath Material:
    High temperature resistant polyvinyl chloride (PVC)
    Filler Material:
    N/A
    Braiding Material:
    N/A
    Screen Material:
    N/A
    Armour Material:
    N/A
    Overall Cable Diameter (mm):
    8.3
    Cut Length (m):
    25
    Minimum Bending Radius:
    5 x D
    Nominal Cross Section Area (mm²):
    3 x 1.5
    Diameter of Conductor (mm):
    1.6
    Conductor Cross Section Area (mm²):
    1.5
    Insulation Thickness (mm):
    0.7
    Outer Sheath Thickness (mm):
    0.9
    Net Weight kg per km (kg):
    108
    Outer Sheath Colour:
    White
    Inner Core Colour(s):
    Brown, Blue, Green/Yellow
    Minimum Operating Temperature (ºC):
    -15º C
    Maximum Operating Temperature (ºC):
    90º C
    Maximum Short Circuit Temperature (ºC):
    150º C
    AC Test Voltage (kV):
    2
    Rated Voltage Uo/U (V):
    300/500 V
    Conductor DC Resistance at 20ºC:
    13.3 Ω/km
    Maximum Mass Supportable - Twin flexible cord (kg):
    5
    EV Charging:
    N/A
    Number of Phases:
    Single
    Capacity Ref Method A: 2 cables/single phase AC/DC (A):
    14
    Capacity Ref Method A: 3-4 cables/three phase AC (A):
    13
    Capacity Ref Method B: 2 cables/single phase AC/DC (A):
    16.5
    Capacity Ref Method B: 3-4 cables/three phase AC (A):
    15
    Capacity Ref Method C: 2 cables/single phase AC/DC (A):
    19.5
    Capacity Ref Method C: 3-4 cables/three phase AC (A):
    17.5
    Capacity Ref Method E: 2 cables/single phase AC/DC (A):
    22
    Capacity Ref Method E: 3-4 cables/three phase AC (A):
    18.5
    Capacity Ref Method F: 2 cables/single phase AC/DC or 3 cables/three phase AC flat horizontally spaced (A):
    25.48
    Capacity Ref Method F: 2 cables/single phase AC/DC or 3 cables/three phase AC flat vertically spaced (A):
    22.68
    Capacity Ref Method F: 2 cables/single phase AC/DC flat touching (A):
    22.82
    Capacity Ref Method F: 3 cables/three phase AC flat touching (A):
    20.28
    Capacity Ref Method F: 3 cables/three phase AC trefoil touching (A):
    21
    Voltage Drop per A per m: DC or single phase AC (mV/A/m):
    32
    Voltage Drop per A per m: three phase AC (mV/A/m):
    27
    Capacity Ref Method 100 (A):
    N/A
    Capacity Ref Method 101 (A):
    N/A
    Capacity Ref Method 102 (A):
    N/A
    Capacity Ref Method 103 (A):
    N/A