UK Code:
3183YA
Harmonised Code:
A05V3V3-F
Usage:
Caravans and boats
Standards:
BS 6004:2012
Certifications:
BASEC, CE, HAR, ISO 9001, UKCA
Warranty:
12 Months
Packaging Description:
Drum (tin core, cardboard flanges)
Core Size (mm):
2.5
Number of Strands:
45
Conductor Type:
Fine-Stranded Copper
Conductor Class:
Class 5
Cable Profile:
Round
Low Smoke Zero Halogen:
No
Armoured:
No
Indoor/Outdoor Usage:
Indoor
Insulation Material:
Cold resistant polyvinyl chloride (PVC)
Outer Sheath Material:
Cold resistant polyvinyl chloride (PVC)
Filler Material:
N/A
Braiding Material:
N/A
Screen Material:
N/A
Armour Material:
N/A
Overall Cable Diameter (mm):
10
Cut Length (m):
50
Minimum Bending Radius:
8 x D
Nominal Cross Section Area (mm²):
3 x 2.5
Diameter of Conductor (mm):
2
Conductor Cross Section Area (mm²):
2.5
Insulation Thickness (mm):
0.8
Outer Sheath Thickness (mm):
1.1
Net Weight kg per km (kg):
165
Outer Sheath Colour:
Yellow
Inner Core Colour(s):
Brown, Blue, Green/Yellow
Minimum Operating Temperature (ºC):
-40º C
Maximum Operating Temperature (ºC):
60º C
Maximum Short Circuit Temperature (ºC):
160º C
AC Test Voltage (kV):
2
Rated Voltage Uo/U (V):
300/500 V
Conductor DC Resistance at 20ºC:
7.98 Ω/km
Maximum Mass Supportable - Twin flexible cord (kg):
5
EV Charging:
N/A
Number of Phases:
Single
Capacity Ref Method A: 2 cables/single phase AC/DC (A):
20
Capacity Ref Method A: 3-4 cables/three phase AC (A):
18
Capacity Ref Method B: 2 cables/single phase AC/DC (A):
24
Capacity Ref Method B: 3-4 cables/three phase AC (A):
21
Capacity Ref Method C: 2 cables/single phase AC/DC (A):
27
Capacity Ref Method C: 3-4 cables/three phase AC (A):
25
Capacity Ref Method E: 2 cables/single phase AC/DC (A):
30.8
Capacity Ref Method E: 3-4 cables/three phase AC (A):
26.1
Capacity Ref Method F: 2 cables/single phase AC/DC or 3 cables/three phase AC flat horizontally spaced (A):
36.4
Capacity Ref Method F: 2 cables/single phase AC/DC or 3 cables/three phase AC flat vertically spaced (A):
32.4
Capacity Ref Method F: 2 cables/single phase AC/DC flat touching (A):
32.6
Capacity Ref Method F: 3 cables/three phase AC flat touching (A):
28.08
Capacity Ref Method F: 3 cables/three phase AC trefoil touching (A):
27
Voltage Drop per A per m: DC or single phase AC (mV/A/m):
19
Voltage Drop per A per m: three phase AC (mV/A/m):
16
Capacity Ref Method 100 (A):
N/A
Capacity Ref Method 101 (A):
N/A
Capacity Ref Method 102 (A):
N/A
Capacity Ref Method 103 (A):
N/A