UK Code:
6242B
Harmonised Code:
624-B
Usage:
Lighting circuits
Standards:
BS 7211:2012
Certifications:
BASEC, CE, ISO 9001, UKCA
Warranty:
12 Months
Packaging Description:
Drum (tin core, cardboard flanges)
Core Size (mm):
1
Number of Strands:
1
Conductor Type:
Solid Copper
Conductor Class:
Class 1
Cable Profile:
Flat
Low Smoke Zero Halogen:
Yes
Armoured:
No
Indoor/Outdoor Usage:
Indoor
Insulation Material:
Cross linked polyethylene (PE)
Filler Material:
N/A
Braiding Material:
N/A
Screen Material:
N/A
Armour Material:
N/A
Overall Cable Diameter (mm):
5.0 x 9.2
Cut Length (m):
50
Minimum Bending Radius:
8 x D
Nominal Cross Section Area (mm²):
2 x 1 + 1re
Diameter of Conductor (mm):
1.13
Conductor Cross Section Area (mm²):
1
Insulation Thickness (mm):
0.7
Outer Sheath Thickness (mm):
0.9
Net Weight kg per km (kg):
58
Outer Sheath Colour:
White
Inner Core Colour(s):
Brown
Minimum Operating Temperature (ºC):
-15º C
Maximum Operating Temperature (ºC):
90º C
Maximum Short Circuit Temperature (ºC):
250º C
AC Test Voltage (kV):
2
Rated Voltage Uo/U (V):
300/500 V
Conductor DC Resistance at 20ºC:
18.1 / 18.1 Ω/km
Maximum Mass Supportable - Twin flexible cord (kg):
0
EV Charging:
N/A
Number of Phases:
Single
Capacity Ref Method A: 2 cables/single phase AC/DC (A):
14.5
Capacity Ref Method A: 3-4 cables/three phase AC (A):
13
Capacity Ref Method B: 2 cables/single phase AC/DC (A):
17
Capacity Ref Method B: 3-4 cables/three phase AC (A):
15
Capacity Ref Method C: 2 cables/single phase AC/DC (A):
19
Capacity Ref Method C: 3-4 cables/three phase AC (A):
17
Capacity Ref Method E: 2 cables/single phase AC/DC (A):
21
Capacity Ref Method E: 3-4 cables/three phase AC (A):
18